EXPECTED REDUCTION OF ENERGY NOT SUPPLIED TO CONSUMERS AFTER INSTALLATION THE IDENTIFIERS OF SINGLE-PHASE-TO-EARTH FAULT IN POWER NETWORKS WITH ISOLATED NEUTRAL
Keywords:
identifier of single-phase-to-earth fault, reliability indicators, EENS indicator, electrical power networks of medium voltageAbstract
Statistical researches of failures in medium voltage electrical power networks, which are constructed as overhead
power lines with ACSR wire, show that most failures are due to single-phase-to-earth faults, which under certain
conditions can transit into interphase faults. To reduce the energy not supplied to consumers proposed to install the
special device in the power network. The name of this device is the identifier of single-phase-to-earth fault. It is
shown that if the device is installed on supports of the overhead line of the power network, this can reduce the
expected energy not supplied to consumers (EENS) by up to 32%. Moreover, the shorter the time it takes to locate
the single-phase-to-earth fault in the power network, the greater will be the reduction in the EENS.
References
Bezruchko V. M., Buinyi R. O., Strogii A. Y.,
Tkach V. I. 2018. Application of GSM technology
for identification of phase-to-ground faults in
electric networks with isolated neutral and pin-type
isolation. Technical Electrodynamics. № 5/6. Р. 96-
doi: 10.15407/techned2018.05.096.
Bezruchko V., Buinyi R., Strogii A., Tkach V. 2019.
Іntegration of New Single-Phase-to-Ground Faults
Detection Devices into Existing SmartGrid Systems.
IEEE 6th International Conference on Energy Smart
Systems, ESS. Р. 84-87. doi:
1109/ESS.2019.8764237.
Buinyi R. O., Dіkhtiaruk І. V., Zorіn V. V. 2014. The
automatic sectionalization of the distributing
networks with high voltage of 6–10 kV with
application the disconnectors of new generation.
Technical Electrodynamics. Vol. 3/6. Р. 70-75.
Buinyi R., Zorin V. V., Tislenko V. V. 2014. How to take
into account the distribution of load in distribution
lines 10kv for optimal allocation of switches.
Electrification and automation of agriculture.
Vol. 99, Р. 1-16.
Farajollahi M., Fotuhi-Firuzabad M., Safdarian A. 2019.
Sectionalizing Switch Placement in Distribution
Networks Considering Switch Failure. IEEE
Transactions on Smart Grid. Vol. 10, Р. 1080-1082.
doi: 10.1109/TSG.2018.2867199.
Tkach V., Bezruchko V., Buinyi R. 2019. The effect of single-phase-to-ground faults on the operational
reliability indicators of overhead lines 6-10 kV
PJSC «Chernigivoblenrego». Bulletin of NTU
"KhPI". № 1. Р. 120-126. doi:10.20998/2413-
2019.01.14.
Zidan A., Khairalla M., Abdrabou A. M., Khlifa T.,
Shaban K., Abdrabou A., Shatshat R. E.,
Gaouda A. M., 2016. Fault Detection Isolation and
Service Restoration in Distribution Systems: State-
of-theArt and Future Trends", IEEE Transactions
on Smart Grid. Vol. 99. Р. 1-16. doi:
1109/TSG.2016.2517620.